Control Devices
Master Electrician Practice study guide with diagrams.
Control Devices
Wyoming Master Electrician Exam — NEC 2023 Study Chapter
Learning Objectives
Upon completing this chapter, you will be able to:
1.1 Scope and Definitions: The Master’s Framework
For the master electrician, "control devices" is not a single article but a coordinated set of rules spanning Article 430 (Motors, Motor Circuits, and Controllers), Article 440 (Air-Conditioning and Refrigeration Equipment), and Article 409 (Industrial Control Panels). The 2023 NEC maintains the critical distinction between a controller (any device that governs the starting, stopping, or reversing of a motor) and a disconnecting means (a device that isolates the motor and controller from the circuit for maintenance).
Key Definitions (paraphrased from Article 100):
Master’s Note: The single most common code violation on commercial sites is the failure to provide a manual disconnect for the control circuit that is separate from the motor’s line-side disconnect, or the failure to ensure that the control circuit disconnect opens all ungrounded conductors of the control circuit simultaneously.
1.2 Motor Controllers: Sizing and Ratings (NEC 430.82 – 430.84)
A motor controller must have a horsepower (hp) rating that is not less than the horsepower rating of the motor, per 430.83(A). This is a strict minimum. For a master supervising a job, you must verify the nameplate of the motor against the controller’s marking.
Exceptions and Special Cases:
For the Master Exam: Do not confuse the controller rating with the branch-circuit short-circuit and ground-fault protective device (BCSCGFPD) sizing. The controller is sized by horsepower, while the protective device is sized by full-load current (FLC) from Table 430.247 (DC), 430.248 (single-phase AC), or 430.250 (three-phase AC). The FLC tables are used for conductor sizing and protection, not the nameplate current, unless the nameplate is higher.
1.3 Control Circuit Conductors and Protection (430.71 – 430.74)
This is a high-yield area for the Wyoming Master exam. Control circuits are classified into two types:
Conductor Sizing (430.72(A)): Control circuit conductors must be sized at not less than 1/3 of the rating of the motor’s branch-circuit protective device, but never smaller than 14 AWG for copper (unless specifically permitted for electronic circuits). If the control circuit is tapped from the motor branch circuit, the tap must be protected per the 1/3 rule.
Overcurrent Protection (430.72(B)): The control circuit must be protected against overcurrent. If the control device (e.g., a relay or contactor coil) is rated for it, you may use a supplementary protector. The critical rule is that the control circuit cannot be connected to the load side of the motor’s branch-circuit short-circuit protective device unless the control circuit has its own overcurrent protection, or the combined rating of the control circuit and the motor does not exceed the branch circuit device rating.
The "Single-Phase" Trap: If a control circuit is connected across two phases of a 3-phase motor circuit (e.g., L1 and L2), and the motor is controlled by a magnetic starter, the control circuit must be arranged so that a ground fault in the control circuit does not cause the motor to start unintentionally. This is the classic "control transformer" issue — the master must ensure a control power transformer (CPT) is used to derive a grounded control voltage, or the control circuit must be two-wire with a grounded conductor.
1.4 Disconnecting Means for Controllers (430.102)
The controller must have a disconnecting means that is located in sight from the controller location. "In sight" is defined as visible and not more than 15 m (50 ft) from the equipment.
Critical 2023 NEC Update: The disconnecting means for the controller must disconnect the controller and the motor. However, 430.102(A) requires the disconnect to be in sight from the controller. 430.102(B) requires a disconnect in sight from the motor. If the motor and controller are not in sight of each other, you need two disconnects.
Master’s Supervision Point: On a commercial rooftop, the master must verify that the disconnect for the motor is not just in sight of the motor, but also that the controller (often inside the unit) has its own disconnect or is within sight of the unit-mounted disconnect. A lockable disconnect handle is required if the disconnect is not in sight of the controller.
1.5 Overload Protection and the "Service Factor" Rule (430.32)
Overload relays (heaters) are the primary control devices protecting the motor from running overcurrent. The master must size these based on the nameplate full-load current, not the NEC table current.
Exam Trap: The exam will give you a motor nameplate of 18 A, a service factor of 1.0, and a Table 430.250 FLC of 22 A. The overloads are sized at 115% of the nameplate (18 A × 1.15 = 20.7 A). The branch circuit conductors are sized at 125% of the table FLC (22 A × 1.25 = 27.5 A → 10 AWG). Do not mix these values.
1.6 Air-Conditioning and Refrigeration Equipment (Article 440)
For the master exam, Article 440 is a specialized subset of motor rules. The key is understanding the "combination load" — the compressor motor and the condenser fan motor.
440.12 – Disconnecting Means: The disconnect for a hermetic refrigerant motor-compressor must be rated at not less than 115% of the nameplate rated-load current or the branch-circuit selection current, whichever is greater. For a unit with multiple motors (e.g., compressor and fan), the disconnect must be rated for the sum of all currents.
440.22 – Short-Circuit and Ground-Fault Protection: The BCSCGFPD for a hermetic compressor is based on the branch-circuit selection current (BCSC) which is typically 115% of the rated-load current. The maximum permitted rating is 175% of the BCSC, with a next-higher-standard-size allowance up to 225% if the 175% value fails to start the motor.
Master’s Field Check: For a packaged rooftop unit, the single disconnect on the unit serves as the disconnect for the controller and the motor. The master must verify that the disconnect is a motor-circuit switch rated for the locked-rotor current of the compressor, not just a general-use switch.
1.7 Control Devices in Services and Separately Derived Systems
Control devices are not limited to motor starters. The master must understand how control and protection devices interact with the service and SDS.
Services (Article 230): The service disconnecting means is the ultimate control device. Each service disconnect must be a suitable enclosure, and the number of disconnects is limited to six (230.71). For a master supervising a job, the critical issue is that the service disconnect must be externally operable and must be capable of being locked in the open position.
Generators and Transformers (Article 700, 701, 705, and 450): A separately derived system (SDS) — such as a step-down transformer or a standby generator with a transfer switch — requires a grounding electrode conductor and a bonding jumper at the SDS. The control device here is the overcurrent device on the secondary side.
Feeder Sizing for Control Panels (409.20): For an industrial control panel, the feeder conductors must be sized at 125% of the continuous load plus 100% of the non-continuous load. The master must sum the nameplate ratings of all motors and control transformers inside the panel.
1.8 Overcurrent Protection Coordination (240.12 and 240.87)
While not strictly a "control device," the master must understand the coordination of overcurrent devices to supervise the installation of control panels and motor control centers (MCCs).
1.9 Code Navigation — Where to Find It
| Concept | NEC 2023 Reference |
|---|---|
| Motor controller rating | 430.82, 430.83 |
| Control circuit conductors | 430.71, 430.72 |
| Disconnect for controller | 430.102(A) |
| Disconnect for motor | 430.102(B) |
| Overload sizing (service factor) | 430.32(A), (C) |
| Full-load current tables (3-phase) | Table 430.250 |
| Full-load current tables (single-phase) | Table 430.248 |
| Hermetic compressor (A/C) | 440.12, 440.22 |
| Industrial control panels | Article 409 |
| Transformer protection (SDS) | 450.3 |
| Generator protection | 445.12 |
| Selective coordination (life safety) | 700.28, 240.12 |
| Arc-flash reduction (1200 A+) | 240.87 |
| Service disconnects (max six) | 230.71 |
| "In sight" definition | Article 100 |
1.10 Inspection and Supervision Points
As a master electrician signing off on work, you must physically verify the following on every motor and control installation:
1.11 Common Exam Traps
Summary
The master electrician’s role in control devices is to bridge the gap between the schematic diagram and the physical installation. You must ensure that the controller is properly rated for the motor, that the control circuit is independently protected, and that the disconnecting means is correctly located and rated. The 2023 NEC places significant emphasis on the separation of the control circuit from the power circuit, and the master must verify that all field wiring complies with the tap rules of 430.72. By mastering the relationship between Table 430.250, the nameplate data, and the specific requirements of Articles 430, 440, and 409, you will be prepared to sign off on complex commercial and industrial installations with confidence.
Preparing for the Wyoming Master Electrician license?
See the full licensing path, exam format, eligibility and application steps.
Ready to test this chapter?
Practice with exam-aligned questions and timed simulations.
Start Practicing Free