Equipment for General Use
Master Electrician Practice study guide with diagrams.
Equipment for General Use
Delaware Master Electrician Exam — Open Book (2023 NEC)
Learning Objectives
By the end of this chapter, you will be able to:
1.1 Motors — Article 430
For a master, motor work is not just about wiring a contactor. It is about the entire circuit — from the branch-circuit overcurrent device back to the feeder and transformer.
1.1.1 Motor Full-Load Current (FLC) vs. Nameplate
The most common field error is using the motor nameplate current to size conductors and short-circuit protection. You must use the FLC tables (Tables 430.247 through 430.250) for conductor sizing and branch-circuit protection. The nameplate is used only for overload relay selection (430.32) and for the motor disconnect rating.
Master trap: For a 3-phase, 460 V motor, the FLC from Table 430.250 is often lower than the nameplate. If you size the branch circuit from the nameplate, you will oversize conductors and protection — which is legal but often unnecessary. The reverse (undersizing) is a violation.
1.1.2 Branch-Circuit Conductors (430.22)
Conductors supplying a single motor must have an ampacity of not less than 125% of the motor FLC. For a motor used in a continuous-duty application, this is the minimum.
For multiple motors on one branch circuit (430.24), the conductor ampacity must be the sum of:
1.1.3 Overload Protection (430.32)
Overload devices protect the motor, the conductor, and the controller from excessive heating due to running overloads. They are not short-circuit protection.
Master trap: Overload relays are sized from the nameplate, not the table FLC. A motor with a 1.0 service factor and a 40°C rise requires a lower overload setting than a "standard" motor.
1.1.4 Short-Circuit and Ground-Fault Protection (430.52)
The branch-circuit fuse or breaker protects the conductors and equipment against short circuits. The maximum permitted rating is based on a percentage of the FLC from the tables:
If these values do not permit the motor to start, the code allows an increase, but the absolute maximums are:
Coordination trap: For a motor with an FLC of 20 A, an inverse-time breaker is permitted at 50 A (250%). If the motor stalls on start, you may go up to 80 A (400%). But increasing the breaker reduces the protection for the conductors — the conductors must still be protected by the breaker's rating.
1.1.5 Motor Feeder Protection (430.62)
The feeder overcurrent device protecting two or more motors must be sized at the sum of the branch-circuit protection ratings of all motors, plus the sum of the FLCs of any other loads. However, you may apply a demand factor — the feeder device can be sized at the largest branch-circuit device plus the sum of the FLCs of all other motors.
Master trap: Do not size the feeder protection from the sum of the motor FLCs. You must use the branch-circuit protection ratings (fuse/breaker sizes), not the conductor ampacities.
1.1.6 Disconnecting Means (430.102)
A disconnect must be located in sight from the motor and the driven machinery. "In sight" means within 15 m (50 ft) and visible. The disconnect must open all ungrounded conductors simultaneously. For a motor over 100 HP, a motor-circuit switch is not sufficient — you need a controller rated for the motor.
1.2 Transformers — Article 450
Transformers are the heart of commercial and industrial systems. A master must verify the installation from the primary side to the secondary.
1.2.1 Overcurrent Protection (450.3)
The rules depend on whether the transformer is primary-only protected or has primary and secondary protection.
Master trap: For a 75 kVA, 480 V to 208Y/120 V transformer:
If you install a 125 A primary breaker, you still need secondary protection because the secondary conductors are not protected by the primary device.
1.2.2 Secondary Conductors (240.21(C))
The secondary conductors of a transformer are treated like a tap. They must terminate in a single OCPD, and the length of the secondary conductors cannot exceed 7.5 m (25 ft) unless they meet specific conditions. For a master, this means you cannot run secondary conductors 30 m to a panelboard without a main breaker at the transformer.
1.2.3 Grounding and Bonding (250.30)
A transformer secondary is a separately derived system. The system must have:
Master trap: A transformer with a 480 V delta primary and a 208Y/120 V secondary requires a system bonding jumper at the transformer. If you bond the neutral at the panelboard instead, you create a parallel path for neutral current on the grounding conductors — a violation of 250.6 and a shock hazard.
1.2.4 Ventilation and Clearances
Transformers must be installed so they are accessible for inspection and maintenance. The working space requirements of 110.26 apply. Dry-type transformers must have ventilation openings that are not blocked. For transformers over 112.5 kVA, the surrounding clearances must be at least 300 mm (12 in.) from combustible materials.
1.3 Generators — Article 445
Generators are treated as separately derived systems when they have no direct connection to the utility source (i.e., they are not operating in parallel).
1.3.1 Nameplate and Ratings
Every generator must have a nameplate showing the rated voltage, current, power factor, and frequency. The ampacity of the conductors from the generator terminals to the first OCPD must be not less than 115% of the generator nameplate current (445.13).
1.3.2 Overcurrent Protection
Generators must be protected from overloads. The OCPD must be rated at not more than 115% of the generator's rated current. If the generator is a stand-alone unit with its own integral protection, the external OCPD may be omitted.
1.3.3 Transfer Switches
Generators used for standby power must be connected through a transfer switch that prevents backfeeding the utility. The transfer switch must be rated for the load and must be a listed device. For a master, the critical issue is the neutral switching:
Master trap: If you use a 3-pole transfer switch on a separately derived generator, you create a parallel neutral path. The generator neutral must be switched to prevent the utility neutral from being connected to the generator's grounded conductor.
1.4 Services and Service Equipment — Article 230
Service work is the highest-liability work a master performs. Errors here affect the entire building.
1.4.1 Number of Services
A building can be served by only one service unless specific exceptions apply (230.2). Additional services are permitted for:
1.4.2 Service Disconnects
The service disconnecting means must disconnect all ungrounded conductors. For a service with more than one disconnect, the disconnects must be grouped in one location. Each disconnect must be rated for the connected load.
Master trap: The six-disconnect rule (230.71) allows up to six disconnects for a service. However, if you have a 4,000 A service with six 800 A disconnects, each disconnect must have a rated interrupting capacity sufficient for the available fault current at the service.
1.4.3 Service Conductors
Service conductors must be sized per Article 220. The minimum size is based on the calculated load, but the ampacity must be sufficient for the load. For a service over 800 A, the conductors must be sized for the calculated load plus a demand factor.
Master trap: For a commercial building with a calculated load of 1,200 A, you cannot use parallel sets of 500 kcmil conductors unless you verify the ampacity adjustment for more than three current-carrying conductors in a raceway.
1.5 Overcurrent Protection Coordination
1.5.1 Selective Coordination (240.12)
For emergency systems, legally required standby systems, and critical operations power systems (COPS), overcurrent devices must be selectively coordinated. This means that when a fault occurs, only the device nearest the fault opens — not the upstream feeder breaker.
Master trap: A master must verify that the time-current curves of the branch breaker and the feeder breaker do not overlap. For example, a 100 A feeder breaker with a 20 A branch breaker: if the branch breaker's instantaneous trip is set at 500 A, and the feeder breaker's instantaneous trip is at 400 A, a 450 A fault will trip both breakers. This is a coordination failure.
1.5.2 Interrupting Rating (110.9)
Every overcurrent device must have an interrupting rating not less than the available fault current at its terminals. For a service with a utility transformer, the available fault current is often 10,000 A to 50,000 A. A standard 10 kAIC breaker is not sufficient for a service.
Master trap: When you replace a breaker in an existing panelboard, you must verify the panelboard's interrupting rating. If the available fault current has increased (due to a larger utility transformer), the existing panelboard may be inadequate.
1.6 Feeders and Branch Circuits — Article 215 and 210
1.6.1 Feeder Sizing (215.2)
Feeder conductors must have an ampacity of not less than 125% of the continuous load plus 100% of the non-continuous load. For a commercial kitchen with a 100 A continuous load, the feeder must be sized for 125 A.
1.6.2 Branch Circuits (210.19)
Branch-circuit conductors must be sized for the load they serve. For a continuous load (e.g., lighting for 3 hours or more), the branch circuit must be rated at 125% of the continuous load. This means a 20 A branch circuit can supply a maximum of 16 A of continuous load.
Master trap: A 2,000 W electric heater on a 120 V circuit draws 16.7 A. This is a continuous load (heating is considered continuous). The branch circuit must be rated at 125% of 16.7 A = 20.8 A → a 25 A branch circuit is required, not a 20 A.
1.7 Code Navigation — Where to Find It
| Topic | NEC Reference |
|---|---|
| Motor FLC tables | Tables 430.247–430.250 |
| Motor branch-circuit conductors | 430.22 |
| Motor overload protection | 430.32 |
| Motor short-circuit protection | 430.52 |
| Motor feeder protection | 430.62 |
| Motor disconnects | 430.102 |
| Transformer protection | 450.3 |
| Transformer secondary taps | 240.21(C) |
| Separately derived systems grounding | 250.30 |
| Generator conductors | 445.13 |
| Number of services | 230.2 |
| Service disconnects | 230.71 |
| Selective coordination | 240.12 |
| Interrupting rating | 110.9 |
| Feeder sizing | 215.2 |
| Branch-circuit continuous loads | 210.19(A) |
| Standard OCPD sizes | 240.6(A) |
| Working space | 110.26 |
| Demand factors (commercial) | Table 220.44 |
1.8 Inspection and Supervision Points
As a master, you are responsible for the final sign-off. On site, verify:
1.9 Common Exam Traps
Summary
This chapter covered the core equipment rules a Delaware Master Electrician must know to supervise installations. The key to the open-book exam is not memorizing every number but knowing which table or section to open and how to apply the adjustment factors. Practice navigating the NEC quickly: for any motor question, go to Article 430; for any transformer, Article 450; for any service, Article 230. The master's edge is in the details — the 125% factors, the FLC tables, and the coordination requirements.
Preparing for the Delaware Master Electrician license?
See the full licensing path, exam format, eligibility and application steps.
Ready to test this chapter?
Practice with exam-aligned questions and timed simulations.
Start Practicing Free