Chapter X

Feeders

Master Electrician Practice study guide with diagrams.

Feeders

Learning Objectives

Upon completing this chapter, you should be able to:

4.Define a feeder per the NEC and distinguish it from a branch circuit and a service conductor.
5.Apply the minimum feeder sizing rules, including the 125% continuous load factor and the impact of voltage drop.
6.Calculate feeder ampacity for 3-phase, 4-wire systems serving linear and nonlinear loads, correctly applying the neutral conductor rules.
7.Size feeders for motor loads, including multiple motors and mixed loads, using the appropriate demand factors from Article 430.
8.Identify the requirements for separately derived systems (transformers and generators) as they apply to feeder grounding, bonding, and overcurrent protection.
9.Navigate the NEC efficiently to locate feeder-related requirements for commercial and industrial installations.
10.Recognize common code traps and inspection points specific to feeder installations.

1.1 The Feeder Defined: Scope and Boundaries

The NEC defines a feeder as all circuit conductors between the service equipment, the source of a separately derived system, or other power supply source, and the final branch-circuit overcurrent device. This is a critical boundary definition. In practice, the feeder begins at the load side of the service disconnect or at the terminals of a transformer secondary, and it ends at the overcurrent device protecting the branch circuits.

A master electrician must be able to instantly classify conductors on a one-line diagram. A conductor supplying a panelboard that, in turn, supplies luminaires and receptacles is a feeder. The conductors from that panelboard to the individual luminaires are branch circuits. The conductors from the utility transformer to the service disconnect are service conductors, not feeders. This distinction drives which set of rules applies.

Key Point: The feeder is the workhorse of a distribution system. It is where the majority of system coordination and voltage-drop decisions are made.


1.2 Sizing and Ampacity: The Core Calculation

Feeder Sizing: 215.2 Core — Master Depth Feeder Sizing: 215.2 Core NEC 2023 · NH Master · Open-Book Theory STEP 1 — LOAD TALLY Noncontinuous loads: Motors, welders, some HVAC Continuous loads (≥3 hr): Lighting, some process equip. Formula: I-feeder = I-noncont + 1.25 × I-cont STEP 2 — 215.2(A)(1) Feeder conductor ampacity ≥ 100% noncontinuous + 125% continuous Size from 75°C column: Table 310.16, 75°C terminals Mandatory — not optional Applies before any voltage drop EXCEPTION No. 1 Entire assembly listed for continuous operation at 100% of rating: 125% factor → drops Straight sum: I-non + I-cont 800 A-class switchgear common STEP 3 — CONDUCTOR SIZING VISUAL Phase A — 75°C col. Phase B — 75°C col. Phase C — 75°C col. Ampacity ≥ calculated load per Table 310.16 INFO NOTE — 215.2(A)(1) 3% feeder / 5% total VD Recommendation only STANDARD vs EXCEPTION — SAME LOAD Standard: I-nc + 1.25 × I-c Exception 1: I-nc + I-c (smaller wire) 125% factor adds 25% MORE conductor capacity Master Electrician Practice — NEC 215.2 feeder conductor sizing · NH Master Theory

1.2.1 Minimum Size (Article 215.2)

The minimum feeder conductor size, before any adjustment or correction factors, must have an ampacity of not less than the sum of two components:

100% of the noncontinuous load
125% of the continuous load

This is the foundational rule. The 125% factor for continuous loads is a heat-management requirement, ensuring the conductor does not operate at its thermal limit for extended periods (3 hours or more). The calculation is based on the load, not the overcurrent device.

Example: A 3-phase, 4-wire feeder supplies a 120/208V panelboard. The calculated load is 150A continuous and 50A noncontinuous.

Minimum ampacity = (150A × 1.25) + 50A = 187.5A + 50A = 237.5A.
The conductor must have an ampacity of at least 238A before any temperature or bundling adjustments.

1.2.2 The 800A Exception (215.2(A)(1) Exception No. 1)

For feeders supplying loads that are either all noncontinuous or where the overcurrent device is rated 800A or less, the 125% factor may be applied to the overcurrent device rating instead of the load. This is a practical allowance. If the OCPD is 800A or less, the feeder is sized to the OCPD, which inherently provides the 125% factor for continuous loads.

Trap: This exception does not apply to feeders supplying a mix of continuous and noncontinuous loads where the OCPD exceeds 800A. In those cases, you must calculate the load precisely.

1.2.3 Voltage Drop (215.2(A)(1) Informational Note, 210.19(A) Informational Note)

The NEC does not mandate a specific voltage drop percentage for feeders as a code requirement, but the informational notes recommend a maximum of 3% for feeders and a total of 5% for feeders plus branch circuits. While informational notes are not enforceable code, a master electrician must treat them as a design standard. For long runs, the calculated ampacity may be insufficient. You must increase the conductor size to limit voltage drop. This is a supervision point: always verify the actual length of the feeder run on the plans.

Formula for 3-phase: VD = (1.732 × K × I × L) / Cmils, where K is the conductor resistivity (approximately 12.9 for copper, 21.2 for aluminum), I is the current, L is the one-way length in feet, and Cmils is the circular mil area of the conductor.


1.3 The Neutral Conductor: Nonlinear Loads and Harmonics

Neutral Sizing: 70% Trap Neutral Sizing: 70% Trap NEC 220.61(A)(B)(C) — 2023 NFPA 70 — NH Master Electrician ACT 1 — 220.61(A) Start: max unbalanced load between neutral & any one ungrounded conductor. Phase A + B + C loads measured Phase A Phase B Phase C Neutral Unbalanced current returns on neutral ACT 2 — 220.61(B) 70% demand factor applies to: • Unbalanced portion above 200 A • Range/dryer portions Feeder neutral demand may be reduced 400 A unbalanced example First 200 A → 100% = 200 A Next 200 A → 70% = 140 A Neutral demand = 340 A ✓ ACT 3 — 220.61(C) NO reduction for: • 3-wire wye circuit portions • Nonlinear loads on 4-wire wye Harmonic currents void the 70% factor ⚠ VFD / LED harmonic loads Triplen harmonics add on neutral Neutral demand stays at 400 A 70% factor PROHIBITED 310.15(E) — Current-Carrying Conductors • Neutral with ONLY unbalanced linear load → NOT counted for derating purposes • Neutral carrying harmonic current → IS counted as current-carrying 4-wire wye with harmonics: Phase A Phase B Phase C Neutral (harmonic) → 4 conductors = 80% per Table 310.15(C)(1) Table 250.102(C)(1) — Absolute Floor for Grounded Service Conductor Even with 70% demand or linear loads, the grounded conductor can never be smaller than Table 250.102(C)(1) requires Master Electrician Practice — NEC 220.61 / 310.15(E) / 250.102(C)(1) — Neutral Sizing 70% Trap

1.3.1 Basic Sizing (215.2(A)(2))

The neutral conductor must be sized to carry the maximum unbalanced load. For a 3-phase, 4-wire wye system supplying line-to-neutral loads, this is the maximum calculated load on any single phase.

1.3.2 The 70% Rule for Nonlinear Loads (220.61(C)(1))

This is a critical master-level distinction. In a 3-phase, 4-wire wye system where the major portion of the load consists of nonlinear loads (e.g., electronic ballasts, VFDs, computers, LED drivers), the neutral conductor must be considered a current-carrying conductor. Triplen harmonics (3rd, 9th, 15th) are zero-sequence currents that do not cancel on the neutral; they add arithmetically.

The code permits the neutral to be sized at 70% of the phase conductor ampacity for this scenario, but only if the neutral is not counted as a current-carrying conductor for ampacity adjustment purposes. This is a complex interaction.

Supervision Point: On a job site, if you see a feeder with a neutral that is visibly smaller than the phase conductors, you must verify that the load is not predominantly nonlinear. If it is, the neutral may overheat. The 70% rule is a minimum, not a recommendation.

1.3.3 Neutral as a Current-Carrying Conductor (310.15(E))

For ampacity adjustment (the "bundle" derating), the neutral is counted as a current-carrying conductor when:

It carries the unbalanced current from line-to-neutral loads.
The major portion of the load is nonlinear (per 220.61(C)(1)).

Trap: In a 3-phase, 4-wire wye feeder supplying only line-to-line loads (e.g., a 3-phase motor), the neutral is not a current-carrying conductor. It is only a grounding/bonding conductor or an equipment grounding conductor. Do not count it for derating.


1.4 Motor and Mixed Load Feeders (Article 430)

Motor Feeder Ampacity — NEC 430.24 & 430.62(A) Multi-Motor Feeder Sizing Motor Feeder Ampacity — NEC 430.24 Three motors on one feeder — 460V, 3-phase, 2023 NEC / NFPA 70 MOTOR 1 10 hp FLC = 14 A MOTOR 2 15 hp FLC = 21 A MOTOR 3 25 hp FLC = 34 A LARGEST 125% largest FLC + 100% others 34 × 1.25 + 21 + 14 = 77.5 A Conductor size per Table 310.16: 4 AWG THHN — 85 A @ 75°C 75°C column per 110.14(C) termination limit Branch device — 25 hp motor Inverse-time breaker: 250% × 34 A = 85 A → next standard 90 A NEC 430.52(C)(1), Table 430.52 Feeder device — all motors Largest branch device + others 90 A + 21 A + 14 A = 125 A Feeder breaker = 125 A max Feeder: 4 AWG THHN Protection: 125 A breaker Meets 430.24 & 430.62(A) If non-motor loads share this feeder, NEC 430.25 (continuous) and 430.26 (non-continuous) apply: general loads are added at 100% (or 125% continuous) on top of the motor demand. Motor demand + general loads → then size feeder per 430.24 + 220.87, not just the motor formula. ! Master Electrician Practice — NEC 430.24 / 430.62(A) motor feeder sizing, 2023 NEC

Feeder sizing for motors is a specialized calculation that departs from the general load-based approach.

1.4.1 Feeder Ampacity for Multiple Motors (430.24)

The feeder supplying two or more motors must have an ampacity of not less than:

125% of the full-load current (FLC) of the highest-rated motor in the group, plus
100% of the FLC of all other motors in the group.

Important: Use the FLC from the tables in Article 430 (e.g., Table 430.250 for 3-phase AC motors), not the nameplate rating. The nameplate is for overload protection; the tables are for conductor sizing and overcurrent protection.

1.4.2 Feeder Ampacity for Mixed Loads (430.25 and 430.26)

When a feeder supplies a motor load plus other loads (lighting, heating, etc.), the calculation is:

58.Calculate the motor load per 430.24.
59.Calculate the other loads per Article 220.
60.Add them together. The motor load is considered a continuous load for this purpose.

1.4.3 Feeder Overcurrent Protection (430.62)

The feeder overcurrent device (the breaker or fuse protecting the feeder) must be sized to carry the motor load. The maximum size is:

The rating of the motor branch-circuit overcurrent device (from 430.52, typically 250% for inverse-time breakers) for the largest motor, plus
The sum of the FLC of all other motors supplied by the feeder.

This is a coordination rule. The feeder OCPD must allow the largest motor to start without opening, but it must not exceed the sum of the largest motor's branch-circuit protection and the running current of all other motors.

Trap: The feeder OCPD is not sized at 125% of the largest motor. That is the branch-circuit rule. The feeder rule uses the maximum branch-circuit protective device rating for the largest motor.


1.5 Separately Derived Systems: Transformers and Generators

A separately derived system (SDS) is a source of power with no direct electrical connection to the supply conductors. The most common SDSs are transformers and generators. The feeder originating from an SDS has specific grounding and bonding requirements.

1.5.1 Grounding and Bonding (250.30)

At the SDS (the transformer secondary or the generator output), you must:

72.Ground the system: Connect the grounded conductor (neutral) to a grounding electrode conductor (GEC) and a grounding electrode (e.g., a ground rod or building steel). This establishes the system's ground reference.
73.Bond the equipment: Connect the non-current-carrying metal parts (enclosures, conduit) to the grounded conductor and the grounding electrode. This creates a low-impedance path for fault current.

Critical Master Point: The neutral-to-case bond at the SDS is made at the source (the transformer or generator) or at the first disconnecting means of the SDS, but not at both. If you bond at both locations, you create a parallel path for neutral current on the equipment grounding conductors, which is a code violation and a safety hazard.

1.5.2 The 5-Foot Rule (250.30(A)(1) Exception)

The bonding jumper at the SDS can be located at the source or at the first disconnecting means. If it is at the first disconnecting means, the grounded conductor must be run with the phase conductors to that point. The exception allows the GEC to be connected to the grounded conductor at the source, but the bonding jumper must be sized per Table 250.102(C)(1).

1.5.3 Transformer Feeder Protection (240.21(C))

The primary overcurrent protection for a transformer can protect the secondary feeder, but only under specific conditions. The most common allowance is the "primary plus secondary" rule:

The primary OCPD must be rated at or below 250% of the transformer's primary full-load current.
The secondary conductors must terminate in a single OCPD that is sized per the secondary ampacity.

If the primary OCPD exceeds 250% of the primary FLC, you must provide secondary protection. This is a complex area that requires careful table work (Table 450.3(B)).

Supervision Point: On a transformer installation, verify the location of the system bonding jumper. It should be clearly identified with a green screw or a clearly marked bonding jumper. Check that the grounded conductor is not bonded to the enclosure at the downstream panelboard.


1.6 Commercial and Industrial Installations

1.6.1 Demand Factors (Article 220)

For commercial feeders, you must apply the demand factors from Part III of Article 220. This includes:

Table 220.42: Lighting load demand factors.
Table 220.44: Receptacle load demand factors.
220.61: Neutral load calculations.

A master must be able to calculate a feeder for a restaurant, a school, or an office building, applying the appropriate demand factors to avoid oversizing.

1.6.2 Kitchen Equipment (220.56)

For commercial kitchens, the feeder can be sized based on the maximum load that can be operated simultaneously, rather than the sum of all equipment. This requires a load management plan or a clear understanding of the kitchen's operation.

1.6.3 Continuous vs. Noncontinuous (Article 100)

The definition of a continuous load is a load where the maximum current is expected to continue for 3 hours or more. This is a judgment call. A master must classify loads correctly. For example, a parking lot lighting circuit that runs all night is continuous. A convenience receptacle circuit is typically noncontinuous.


1.7 Code Navigation: Where to Find It

ConceptNEC 2023 Location
Feeder DefinitionArticle 100
Minimum Feeder Size215.2(A)(1)
Feeder Neutral Size215.2(A)(2), 220.61
Feeder Overcurrent Protection215.3
Motor Feeder Sizing430.24, 430.25
Motor Feeder OCPD430.62
Conductor Ampacity TablesTable 310.16, 310.17
Ampacity Adjustment Factors310.15(B)
Neutral as Current-Carrying310.15(E)
SDS Grounding & Bonding250.30
Transformer Protection450.3, 240.21(C)
Demand Factors (Commercial)Part III of Article 220
Voltage Drop (Informational)215.2(A)(1) Info Note

1.8 Inspection and Supervision Points

As a master, you are responsible for the final sign-off. On a feeder installation, you must verify:

101.Conductor Size: Confirm the conductor ampacity is correct for the calculated load, including the 125% continuous factor. Check the nameplate of the panelboard or the load schedule.
102.Termination Temperature Rating: If the feeder terminates on equipment rated 60°C, you cannot use the 75°C or 90°C ampacity column. This is a common cause of undersized conductors. Check the equipment labeling.
103.Bundling and Derating: Count the number of current-carrying conductors in the conduit or cable. Apply the adjustment factors from Table 310.15(B)(3)(a). Remember to count the neutral if the load is nonlinear.
104.Grounding and Bonding: At a separately derived system, verify the single-point bond. Check the size of the GEC and the bonding jumper per Table 250.66 and 250.102(C)(1).
105.Overcurrent Device Rating: Verify the feeder breaker or fuse is sized correctly for the conductor ampacity after derating, and that it is coordinated with the branch-circuit devices downstream.
106.Voltage Drop: For long runs, measure the voltage at the end of the feeder under full load. It should not exceed 3% of the nominal voltage.

1.9 Common Exam Traps

109.The 125% Trap: Applying the 125% factor to the overcurrent device instead of the load for a standard feeder. The rule is 125% of the continuous load.
110.The Motor FLC Trap: Using the motor nameplate current instead of the table FLC (Table 430.250) for feeder sizing.
111.The Neutral Trap: Forgetting to count the neutral as a current-carrying conductor when the load is nonlinear, leading to an under-sized neutral and an incorrect derating calculation.
112.The SDS Bonding Trap: Assuming the neutral is bonded to the ground at the main panelboard of a building when it is fed from a transformer. The bond must be at the transformer or the first SDS disconnect, not both.
113.The 800A Exception Trap: Applying the 800A exception to a feeder with a mix of continuous and noncontinuous loads when the OCPD is rated over 800A. This is not permitted.
114.The Voltage Drop Trap: Assuming voltage drop is a code requirement. It is a design consideration, but a master is expected to know the recommended limits and how to calculate them.

1.10 Summary

The feeder is the backbone of any electrical distribution system. Master-level knowledge requires moving beyond simple ampacity calculations to a full understanding of load characterization (continuous vs. noncontinuous), harmonic effects on the neutral, motor load calculations, and the unique grounding and bonding rules for separately derived systems. The ability to navigate the NEC quickly and accurately—knowing that Article 215 is the primary article for feeders, but that 430, 450, and 250 all have critical feeder-related rules—is the difference between a journeyman and a master. Always verify your calculations with the actual code text during the exam, and apply the same rigor to every field inspection.

Preparing for the New Hampshire Master Electrician license?

See the full licensing path, exam format, eligibility and application steps.

Read the New Master Electrician guide

Ready to test this chapter?

Practice with exam-aligned questions and timed simulations.

Start Practicing Free