Chapter III

Feeders

Master Electrician Practice study guide with diagrams.

Feeders

Learning Objectives

Upon completing this chapter, you will be able to:

4.Define a feeder per the NEC and distinguish it from a branch circuit and a service conductor.
5.Apply the minimum feeder sizing rules, including the 100% non-continuous plus 125% continuous load calculation.
6.Calculate feeder conductor ampacity adjustments and corrections for ambient temperature and conductor bundling.
7.Size the feeder neutral (grounded conductor) and understand when reduced neutrals are permitted.
8.Apply feeder overcurrent protection requirements, including the "next size up" rule for standard ampere ratings.
9.Understand feeder requirements for specific occupancies and systems, including services, separately derived systems, and motor loads.
10.Identify the key code sections for feeder installation, sizing, and protection in the 2023 NEC.

1.1 Definitions and Scope: Feeder vs. Branch Circuit

The NEC defines a Feeder as all circuit conductors between the service equipment, the source of a separately derived system, or other power supply source, and the final branch-circuit overcurrent device.

Key Distinctions for the Master:

Service Conductors: Run from the utility point of connection to the service disconnecting means.
Feeders: Run from the service disconnecting means (or the terminals of a generator or transformer) to the branch-circuit overcurrent devices.
Branch Circuits: Run from the final overcurrent device to the outlets or loads.

A common field error is misidentifying a conductor that runs from a panelboard to a sub-panel. That is a feeder, not a branch circuit. This distinction is critical because the rules for ampacity, overcurrent protection, and grounding differ.


1.2 Sizing Feeders: The Core Calculation (NEC 215.2)

Feeder Ampacity Deep-Dive: Derating & 90°C Column (NEC 215.2) Feeder Ampacity Deep-Dive: Derating & 90°C Column NEC 215.2(A)(1) — 480V Panel Feeder · Two Feeders, One Conduit · 2023 NEC STEP 1 — Load (215.2(A)(1)) Continuous: 120 A × 125% Noncontinuous: 40 A × 100% = 150 A + 40 A = 190 A minimum STEP 2 — Conductor Count Two 3-phase feeders share one conduit: 2 × 3 conductors = 6 CCCs Conduit — 6 current-carrying conductors STEP 3 — Derating Table 310.15(B)(3)(a): 6 CCCs → 80% adjustment Applied to 90°C column: 3/0 THHN: 225 A × 0.80 225 A × 0.80 = 180 A ✗ 180 A < 190 A — FAILS 4/0 THHN: 260 A × 0.80 = 208 A ≥ 190 A ✓ 110.14(C) — 75°C LIMIT 4/0 @ 75°C = 230 A ≥ 208 A ✓ 215.3 / 240.6(A) Standard 200 A device 4/0 THHN Selected feeder conductor Table 310.16 — 90°C column 3/0 THHN: 225 A 4/0 THHN: 260 A Master Electrician Practice — NEC 215.2 Feeder Sizing · 2023 NEC · ICC 701 Wyoming Master Electrician

The minimum feeder conductor size must have an ampacity sufficient for the load, computed per Article 220. The fundamental rule is found in NEC 215.2(A)(1) :

The ampacity of the feeder conductors shall not be less than the sum of the non-continuous loads plus 125% of the continuous loads.

Continuous Load is defined as a load where the maximum current is expected to continue for 3 hours or more.

Example Calculation:

A commercial kitchen has a non-continuous load of 60 A and a continuous load of 80 A.

Feeder load = 60 A + (80 A × 1.25) = 60 A + 100 A = 160 A.
The feeder conductors must have an ampacity of at least 160 A before any adjustment or correction factors are applied.

Master's Note: This 125% factor is applied to the load, not the conductor. After determining the minimum ampacity, you must then apply ambient temperature correction and conductor bundling adjustment factors from Table 310.16 and its associated correction factors. The final conductor size must satisfy both the load requirement and the adjusted ampacity requirement.


1.3 The Neutral (Grounded) Conductor Sizing

Sizing the Grounded (Neutral) Conductor: 220.61 Sizing the Grounded (Neutral) Conductor — NEC 220.61 208Y/120V Panelboard · 2023 NEC / NFPA 70 · Master Depth 208Y/120V Source A 120V B 120V C 120V N Load Panel L-N Loads A B C N Balanced Loads I_N ≈ I_A + I_B + I_C (phasor) 220.61(A) — Sizing Rule Neutral sized for MAXIMUM unbalanced L-N load I_N = phasor sum of phase currents I_N ≠ I_A + I_B + I_C ⚠ Nonlinear Load Trap Electronic ballasts, VFDs, server supplies generate TRIPLEN HARMONICS (3rd, 9th…) → Add on neutral, NOT cancel Master Checks — Neutral Sizing 1 220.61(A): Size for max unbalanced L-N load Often smaller than phase conductors 2 Nonlinear loads → full-size neutral required Triplen harmonics → I_N can exceed I_phase 3 Derate per 310.15(E) when harmonics present 250.24(C) + Table 250.102(C)(1) Service neutral ≥ Table 250.102(C)(1) minimum (never smaller) 210.4(B) Multiwire Circuit Shared neutral → simultaneous disconnect Master Electrician Practice — NEC 220.61 grounded conductor sizing · 2023 NEC / NFPA 70

The feeder neutral must be sized to carry the maximum unbalanced load. However, the rules are nuanced.

NEC 215.2(A)(2) requires the neutral to have an ampacity not less than the maximum unbalanced load. For a 3-phase, 4-wire system, this is the maximum net calculated load between the neutral and any one ungrounded conductor.

Reduced Neutral:

The neutral is permitted to be smaller than the ungrounded conductors, provided:

37.It carries only the unbalanced load.
38.The load is not a nonlinear load (see below).

The Nonlinear Load Trap:

For feeders serving nonlinear loads (e.g., electronic ballasts, variable frequency drives, computers), the neutral can carry significant triplen harmonics (3rd, 9th, 15th...). These harmonics are additive on the neutral. NEC 310.15(E) requires the neutral to be counted as a current-carrying conductor for ampacity adjustment purposes when serving nonlinear loads. In severe cases, the neutral may need to be full-size or even larger than the phase conductors.

Master's Note: For a feeder supplying a panelboard that feeds data centers or offices with many computers, do not automatically reduce the neutral. Treat it as a current-carrying conductor, which triggers a 50% adjustment factor for four or more current-carrying conductors in a cable or raceway.


1.4 Feeder Overcurrent Protection (NEC 215.3)

Feeder conductors must be protected against overcurrent per their ampacity.

The "Next Size Up" Rule:

Where the calculated ampacity does not correspond to a standard rating of a fuse or circuit breaker, you may use the next higher standard rating, but only if:

47.The next higher rating does not exceed 800 A.
48.The conductor ampacity is sufficient for the connected load.

Standard Ratings (NEC 240.6): 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250, 300, 350, 400, 450, 500, 600, 700, 800, 1000, 1200, 1600, 2000, 2500, 3000, 4000, 5000, 6000.

Example:

A calculated load requires a conductor ampacity of 145 A. You select a 1/0 AWG conductor (150 A at 75°C). The next standard OCPD above 145 A is 150 A. This is permitted because the conductor ampacity (150 A) is equal to the OCPD rating.

Example with a Trap:

A calculated load is 155 A. You select a 2/0 AWG conductor (175 A at 75°C). The next standard OCPD above 155 A is 175 A. This is permitted. However, if you selected a 1/0 AWG (150 A), you cannot protect it with a 175 A breaker because 150 A is less than the calculated load of 155 A.

Tap Rules:

Feeders can be tapped (NEC 240.21(B)) to supply smaller panelboards, but the tap conductors must terminate in a single OCPD and meet specific length and ampacity requirements (e.g., 3 ft, 10 ft, 25 ft rules). A master must know these exceptions for industrial applications where running a full-size feeder to every small load is impractical.


1.5 Feeder Installation Requirements

NEC 215.12 covers the minimum installation requirements:

Wiring Methods: Feeders must be installed using Chapter 3 wiring methods (conduit, cable, busway, etc.).
Minimum Size: Conductors must be at least 8 AWG copper or 6 AWG aluminum for feeders, unless they are tapped from a feeder and terminate in a single OCPD (per 240.21(B)).
Bundling: When feeders are installed in the same raceway or cable, the number of current-carrying conductors determines the adjustment factor per Table 310.15(C)(1) .

Voltage Drop (Informational but Critical):

NEC 215.2(A)(4) Informational Note No. 2 recommends that feeder conductors be sized to limit voltage drop to 3% for the feeder, and the total voltage drop for the feeder and branch circuit to 5%. While this is not a mandatory "shall" requirement, it is a design requirement that a master must address. The exam will test your ability to calculate voltage drop for long runs.

Voltage Drop Formula (Single-Phase):

VD = (2 × K × I × L) / CM

Where K = 12.9 for copper, 21.2 for aluminum; I = current; L = one-way length in feet; CM = circular mils.

Voltage Drop Formula (Three-Phase):

VD = (1.732 × K × I × L) / CM

Master's Note: For a 480 V, 3-phase motor feeder running 400 feet, the voltage drop often dictates a conductor size larger than the ampacity requirement. Always check voltage drop on long runs.


1.6 Feeders for Specific Loads

1.6.1 Motor Feeders (NEC 430.24 and 430.25)

Motor Feeder Sizing: 430.24 Ampacity & 430.62 Ceiling Motor Feeder Sizing — 430.24 Ampacity & 430.62 Overcurrent Ceiling Three 25 hp, 230 V, 3-phase motors — Table 430.250: 68 A each · 2023 NEC / NFPA 70 FEEDER 240.4 applies to conductors 4/0 Cu 75°C = 230 A 25 hp Motor 68 A · 230V 3Φ 25 hp Motor 68 A · 230V 3Φ 25 hp Motor 68 A · 230V 3Φ 175 A 175 A 175 A STEP 1 — Feeder Ampacity per 430.24 Feeder ampacity ≥ (largest motor FLC × 1.25) + sum of other FLCs = (68 A × 1.25) + 68 A + 68 A = 85 + 68 + 68 = 221 A Per Table 310.16 → 4/0 Cu at 75°C = 230 A ≥ 221 A ✓ STEP 2 — Feeder Protection Ceiling per 430.62(A) Largest branch device = 68 A × 250% (Table 430.52, inverse-time) = 170 A → next standard = 175 A (240.6) 430.52(C)(1) Ex. 1 allows next standard; 400% cap = 272 A → 175 A OK 430.62(A) ceiling = 175 A + 68 A + 68 A = 311 A → Largest standard size ≤ 311 A = 300 A (240.6) ⚠ 300 A device requires 300 A conductors (240.4) — 4/0 Cu rated 230 A is insufficient! 430.62(A) sets a MAXIMUM ceiling — not a required minimum OPTION A: Upsize feeder to 350 kcmil (310 A) → 300 A device OK OPTION B: Drop device to 225 A → 4/0 Cu (230 A) suffices Master Electrician Practice — NEC 430.24 & 430.62 motor feeder coordination · ICC 701 (Wyoming) · 2023 NEC

A feeder supplying a group of motors must have an ampacity of at least:

125% of the full-load current (FLC) of the highest-rated motor in the group, plus
The sum of the FLCs of all other motors in the group.

Example:

A feeder supplies three motors: 10 HP (14 A FLC), 15 HP (21 A FLC), and 25 HP (34 A FLC) at 460 V, 3-phase.

Highest motor: 34 A × 1.25 = 42.5 A
Other motors: 14 A + 21 A = 35 A
Total feeder ampacity = 42.5 A + 35 A = 77.5 A.

The feeder OCPD is sized per NEC 430.62, which requires the maximum rating of the feeder protective device to be based on the largest branch-circuit protective device plus the sum of the FLCs of the other motors. This is a coordination issue—the feeder OCPD must allow the largest motor to start without opening, but must protect the feeder.

1.6.2 Transformer Feeders (Separately Derived Systems)

When a feeder supplies the primary side of a transformer, the transformer is a separately derived system. The secondary conductors are a new feeder.

Primary Protection (NEC 450.3): The primary OCPD must protect the transformer against overcurrent. If the primary OCPD is rated at 125% of the primary current (or the next standard size), the secondary conductors may be protected by the primary device under specific conditions (NEC 240.21(C)).

Secondary Conductor Protection: The secondary conductors must be protected by an OCPD on the secondary side, unless they comply with the "secondary conductor tap" rules in NEC 240.21(C) . These rules allow the secondary conductors to be tapped without a secondary OCPD if they terminate in a single OCPD and meet length and ampacity requirements.

Master's Note: For a 75 kVA, 480 V to 208Y/120 V transformer:

Primary current = 75,000 VA / (480 V × 1.732) = 90.2 A.
Primary OCPD = 90.2 A × 1.25 = 112.7 A → next standard size = 125 A.
Secondary current = 75,000 VA / (208 V × 1.732) = 208 A.
Secondary conductors must have an ampacity of at least 208 A (or 260 A if the load is continuous).

1.6.3 Generator Feeders

Generators are also separately derived systems (unless they are non-separately derived, which is rare). The feeder from the generator output terminals to the transfer switch or distribution panel must be sized per the generator's rated output current.

Critical Rule: The generator's rated output is the continuous rating. The feeder must be sized for 125% of the continuous load, but the generator's rated output already includes the continuous rating. Therefore, the feeder ampacity must be at least 100% of the generator's rated output current, but the OCPD must be sized to protect the generator windings.


1.7 Code Navigation: Where to Find It

ConceptNEC 2023 Reference
Feeder DefinitionArticle 100
Feeder Sizing (Minimum Ampacity)215.2(A)(1)
Feeder Neutral Sizing215.2(A)(2)
Feeder OCPD215.3
Standard OCPD Ratings240.6
Feeder Tap Rules240.21(B)
Transformer Secondary Taps240.21(C)
Ampacity TablesTable 310.16
Adjustment Factors (Bundling)Table 310.15(C)(1)
Ambient Temp CorrectionTable 310.15(B)(1)
Nonlinear Load Neutral310.15(E)
Motor Feeder Sizing430.24, 430.25
Motor Feeder OCPD430.62
Transformer Protection450.3
Voltage Drop (Informational)215.2(A)(4) Informational Note No. 2
Load CalculationsArticle 220
Services (Related)Article 230
Grounding & Bonding (Related)Article 250

1.8 Inspection and Supervision Points

As a master electrician, you are responsible for the work being code-compliant. On-site, verify the following:

101.Conductor Size vs. Termination Rating: Check that the conductor ampacity is based on the 75°C column if the terminals are rated 75°C. If the terminals are rated 60°C (common on small breakers), you must use the 60°C column. This is a common source of undersized conductors.
102.Continuous Load Marking: Verify that the OCPD is rated for continuous operation at 100% of its rating. If not, the OCPD must be sized at 125% of the continuous load.
103.Neutral Termination: Ensure the neutral is properly terminated in the neutral bar, not the equipment grounding bar, in the sub-panel. The neutral must be isolated from the enclosure in a sub-panel (separately derived system or feeder).
104.Bonding: Check that the equipment grounding conductor is properly bonded to the enclosure at the service, but not bonded at the sub-panel (unless it is a separately derived system).
105.Mechanical Protection: Verify that feeders are protected from physical damage, especially where they exit raceways or enter enclosures. Check for proper bushings and connectors.

1.9 Common Exam Traps

108.The 125% Trap: Applying the 125% factor to the conductor after calculating the load. The factor is applied to the load, not the conductor.
109.The "Next Size Up" Trap: Using the "next size up" rule when the calculated ampacity is less than the conductor ampacity but the OCPD is oversized. The OCPD must protect the conductor, and the conductor must carry the load.
110.The Neutral Trap: Forgetting to count the neutral as a current-carrying conductor for 3-phase, 4-wire systems with nonlinear loads. This triggers a 50% adjustment factor.
111.The Motor Trap: Forgetting to use 125% of the largest motor, not all motors.
112.The Temperature Trap: Forgetting to apply ambient temperature correction factors when conductors are run through a boiler room or rooftop conduit. The ampacity must be corrected before comparing to the load.
113.The 3-Phase Trap: Using the single-phase voltage drop formula (2 × K × I × L) for a 3-phase circuit. You must use the 3-phase formula (1.732 × K × I × L).
114.The Tap Rule Trap: Assuming a feeder tap can be any length. The 10 ft and 25 ft tap rules have specific requirements for ampacity, termination, and physical protection.

1.10 Summary

Feeder sizing and protection is the heart of commercial and industrial electrical design. A master electrician must be able to:

Calculate the minimum feeder ampacity for continuous and non-continuous loads.
Apply adjustment and correction factors correctly.
Size the neutral for unbalanced and nonlinear loads.
Select the proper OCPD, including the "next size up" rule.
Apply the specific rules for motors, transformers, and generators.
Navigate the NEC efficiently to find the applicable sections.

Mastery of Article 215, combined with a working knowledge of Articles 220, 240, 310, 430, and 450, will allow you to design safe, code-compliant feeder systems and pass the Wyoming Master Electrician exam.

Preparing for the Wyoming Master Electrician license?

See the full licensing path, exam format, eligibility and application steps.

Read the Wyoming Master Electrician guide

Ready to test this chapter?

Practice with exam-aligned questions and timed simulations.

Start Practicing Free