Chapter VII

Motors and Generators

Master Electrician Practice study guide with diagrams.

Chapter 1: Motors and Generators

Learning Objectives

Upon completing this chapter, the candidate will be able to:

4.Apply the general requirements for motor and generator installations, including nameplate data interpretation and terminal housing requirements.
5.Calculate branch-circuit, feeder, and short-circuit/ground-fault protection sizes using the specific tables and percentages required by the NEC.
6.Differentiate between the requirements for a separately derived system (generator) and a non-separately derived system, and apply grounding and bonding rules accordingly.
7.Size conductors for motor loads considering continuous duty, voltage drop, and ambient temperature corrections.
8.Identify coordination requirements for critical operations and the specific allowances for motor overload devices.

1.1 General Installation Requirements (Article 430)

The Master electrician must view Article 430 not as a collection of isolated rules, but as a complete system. The Code requires that each motor have a branch circuit, a disconnecting means, a controller, and overload protection. The failure to coordinate these four elements is a primary source of exam traps.

Nameplate vs. Tables: A critical distinction exists between the motor nameplate current and the table values used for sizing conductors and protection. The full-load current (FLC) used for conductor sizing and branch-circuit protection is taken from NEC Tables 430.247 through 430.250, not the nameplate. The nameplate current is used exclusively for sizing the motor’s overload protection (per 430.32) and for the motor’s actual thermal limits. This is a classic exam trap: using nameplate amps to size a feeder conductor will result in an undersized conductor.

Terminal Housings: For motors larger than 100 hp or for motors with a maximum operating voltage over 600V, the terminal housing must be arranged so that the motor can be serviced without disturbing the connections to the controller (430.12). This is a field inspection point often overlooked on large industrial equipment.


1.2 Motor Circuit Conductors (Part II)

Motor Conductor Sizing (430.22) — Master Depth Motor Conductor Sizing — NEC 430.22(A) 125% of Table FLC (not nameplate) — Continuous Duty MOTOR DATA Motor: 3-phase, 460V, 25 HP Nameplate FLA: 32.0 A Service factor: 1.15 Temp rise: 40°C Table 430.248: FLC @ 460V = 34 A (NOT 32A nameplate) CALCULATION Step 1: 430.22(A) multiplier 34 A × 1.25 = 42.5 A Step 2: 430.22(B) continuous duty 42.5 A minimum ampacity Step 3: 240.4(D) small conductors Next standard OCPD: 45 A (430.52(C) allows 250% max) CONDUCTOR Per Table 310.16 (75°C col): #8 AWG THWN-2 → 50 A ✓ 50 A ≥ 42.5 A Voltage drop (210.19(A) Note 4): 100 ft, 42.5A, Vd = 2×L×I×R/1000 = 4.2V → 0.9% OK — within 3% limit COMPLETE CIRCUIT — 430.22(A) + 430.52 + 250.122 OCPD 45 A #8 THWN-2 MOTOR 25 HP 460V 3ph EGC #10 Cu DISC. 430.102 Source Master Electrician Practice — NEC 430.22(A) motor conductor sizing | Table 430.248 FLC × 125% | Table 310.16 selection KEY: Table FLC, not nameplate

Branch-Circuit Conductors (430.22): The general rule is that conductors supplying a single motor must have an ampacity of not less than 125% of the motor’s FLC as listed in the tables. For a motor used in a continuous duty application, this is the baseline.

Feeder Conductors (430.24): When a feeder supplies several motors, the conductor ampacity must be sufficient for the sum of the FLCs of all motors on the circuit, plus 125% of the FLC of the highest-rated motor in the group. The calculation is:

Sum of all FLCs (from tables) + 25% of the largest motor FLC = Feeder Ampacity.

Application Example: A feeder supplies a 25 hp, 208V, three-phase motor (FLC = 74.8A) and a 10 hp motor (FLC = 30.8A).

Largest motor: 74.8A × 1.25 = 93.5A
Other motor: 30.8A
Total: 93.5 + 30.8 = 124.3A. You would select a conductor with an ampacity of at least 125A (assuming 75°C terminals).

Motor + Loads (430.25): If a feeder supplies a motor and other loads (lighting, heating), the feeder must be sized for the sum of the other loads plus the motor load calculated per 430.24.

Voltage Drop: While the NEC does not mandate a specific percentage for voltage drop in all cases, 210.19(A) Informational Note suggests a maximum of 3% for branch circuits and 5% total. For motor circuits, the Master must account for the inrush current. Conductors must be sized to limit voltage drop to allow the motor to start; a stalled motor drawing locked-rotor current will trip overloads if the voltage collapses.


1.3 Overload Protection (Part III)

Overload Sizing from Nameplate — NEC 430.32(A)(1) vs (A)(2) Overload Sizing from Nameplate NEC 430.32(A)(1) vs (A)(2) — Master depth: nameplate-based OL protection MOTOR NAMEPLATE HP: 25 Volts: 460V 3-Phase FLA: 34.0 A SF: 1.15 Insul: Class F RPM: 1765 Frame: 286T SF ≥ 1.15 NEC 430.32 Service factor? SF ≥ 1.15 125% × FLA SF < 1.15 115% × FLA OVERLOAD RELAY SETTING NEC 430.32(A)(1): OL = 125% × 34.0 A Maximum OL protection: 42.5 A If 42.5A not available → next standard size per NEC 430.32(C) (heater/relay tables) RELAY DIAL — THERMAL OVERLOAD TRIP CLASS 0% 100% 125% 42.5A Trip Class: 20 (default) Trip Class 10 → for fast starts, high inertia loads NEC 430.32(A)(1) + Art 430.44 Master Electrician Practice — NEC 430.32 motor overload protection, 2026 NEC / NFPA 70, TDLR/PSI open-book

Overload protection is designed to protect the motor, the motor control apparatus, and the branch-circuit conductors from excessive heating due to motor overloads and failure to start.

Sizing Rules (430.32):

Motors with a service factor of 1.15 or greater: The overload device shall be sized at no more than 125% of the motor nameplate current rating.
Motors with a temperature rise of 40°C or less: Also sized at no more than 125% of the nameplate current.
All other motors: The overload device shall be sized at no more than 115% of the nameplate current rating.

The "Next Size Up" Rule (430.32(C)): If the standard sizes of overload relays (per 240.6) do not correspond to the calculated value, the next higher standard size is permitted, but only up to a maximum of 140% for motors with a 1.15 service factor, and 130% for all others. This is a specific allowance that does not apply to branch-circuit short-circuit protection.

Dual-Element Fuses vs. Inverse Time Breakers: The Master must understand that overload protection is distinct from short-circuit protection. Overload relays (heaters) are typically provided in the motor starter. If a motor is controlled by a variable frequency drive (VFD), the VFD’s internal electronic overload protection is often acceptable, provided it meets the requirements of 430.124.


1.4 Branch-Circuit Short-Circuit and Ground-Fault Protection (Part IV)

SC/GF Protection Table 430.52 — Motor Branch Circuit Short-Circuit and Ground-Fault Protection SC/GF Protection Table 430.52 NEC 2026 · Motor Branch Circuits · 430.52(C)(1) Exception No. 1 Protective Device Rating Multiplier Max Standard Rating Master-Level Application Notes Non-Time-Delay Fuse NEC 430.52(C)(1) 300% of FLC (Table 430.247–250) Next standard size per 430.52(C)(1) Exception No. 1 • "Next size up" permitted ONLY if standard rating doesn't exceed 300% — max 400% for fuse (430.52(C)(1) Ex. 1) • Must still carry starting current (no nuisance opening) • Round UP to next standard: 15,20,25,30,35,40,45,50,60,70,80,90,100,110,125,150,175,200,225,250,300,350,400,450,500,600 Inverse-Time Breaker NEC 430.52(C)(1) 250% of FLC (Table 430.247–250) Next standard size per 430.52(C)(1) Exception No. 1 • "Next size up" permitted ONLY if standard rating doesn't exceed 250% — max 400% for breaker (430.52(C)(1) Ex. 1) • Thermal-magnetic trip must coordinate with motor starting curve and locked-rotor current Instantaneous-Trip Breaker / Motor Circuit Protector NEC 430.52(C)(3) 800% for motors marked "Instantaneous" No "next size up" per 430.52(C)(3) Must not exceed 800% • Only for motors marked "Instantaneous" or with adjustable instantaneous trip element • Must be adjustable to NOT trip on locked-rotor • Requires short-circuit current rating per 430.52(C)(3) MASTER POINT — 430.52(C)(1) Exception No. 1: Next size up allowed only when the calculated value is NOT a standard rating. If the next standard size exceeds 400% (fuse) or 400% (breaker) of FLC, it is PROHIBITED — must use 400% max or reduce starting current. WORKED EXAMPLE — 430.52 at Master Depth Motor: 25 HP, 3-phase, 460V, Design B FLC per Table 430.250 = 34A Inverse-time breaker: 34A × 250% = 85A → next standard = 90A ✓ Non-time-delay fuse: 34A × 300% = 102A → next standard = 110A ✓ (max 400% = 136A) INTERACTIVE RULE — When "Next Size Up" Fails If calculated value = 150A, next standard = 175A But 175A > 400% of FLC? Check: FLC must be ≥ 43.75A If FLC = 40A: 400% = 160A → 175A PROHIBITED Solution: Use 150A (non-standard, field-assembled) or reduce starting current Master Electrician Practice — NEC 430.52 motor branch-circuit short-circuit and ground-fault protection · TDLR/PSI open-book

This is the most calculation-heavy area for the Master exam. The device protects the conductors, the controller, and the motor against short circuits and ground faults, not overloads.

Sizing Rules (430.52): The maximum rating of the protective device is based on a percentage of the motor FLC (from tables), not the nameplate.

Inverse Time Breaker: 250% of FLC.
Dual-Element (Time-Delay) Fuse: 175% of FLC.
Non-Time-Delay Fuse: 300% of FLC.

The "Next Size Up" Rule (430.52(C)(1)): If the calculated value does not correspond to a standard ampere rating (240.6), the next higher standard size is permitted. However, this allowance is strictly limited. The maximum permitted size is 800% of the FLC for motors other than those with a marked code letter, and specific caps apply based on the motor’s locked-rotor code letter (Table 430.52(B) Note).

Example: A 50 hp, 460V, three-phase motor has an FLC of 65A. Using an inverse time breaker: 65A × 250% = 162.5A. The next standard size up is 175A. This is permitted.

Motor Overload vs. Short Circuit: If the branch-circuit short-circuit protection is sized too low, it will trip on motor starting inrush (locked-rotor current). If sized too high, it may not protect the conductors. The Master must ensure the conductors have an ampacity sufficient for the overload relay setting, but the short-circuit device protects the conductor from fault current.

Coordination (430.52(C)(3)): For "coordinated" systems in critical operations (hospitals, data centers), the branch-circuit protective device may be increased beyond the 800% cap if a short-circuit study demonstrates that the device will clear a fault before the motor starter contacts weld or the conductors are damaged. This requires engineering documentation.


1.5 Disconnecting Means and Controllers (Parts V & VI)

Disconnecting Means (430.101): A disconnecting means must be provided for each motor and controller. The disconnect must be located in sight from the motor and the driven machinery. "In sight" is defined as visible and not more than 15.2 m (50 ft) from the equipment.

Controller Disconnect: The controller disconnect must open all ungrounded supply conductors. For a motor with a rating over 600V, the disconnect must be a circuit breaker or a motor-circuit switch.

Controller Rating (430.83): The controller must have a horsepower rating not lower than the horsepower rating of the motor. A controller rated for a larger motor can control a smaller one. However, a controller with a lower horsepower rating cannot control a larger motor, even if the current rating is sufficient.

Motor Disconnect (430.109): The disconnecting means must be a listed motor-circuit switch, a molded-case circuit breaker, or a listed instantaneous-trip circuit breaker. A general-use switch is only permitted for stationary motors of 2 hp or less.


1.6 Generators and Separately Derived Systems (Article 445 & 250.30)

Generators are the heart of many commercial and industrial installations. The Master must determine if the generator is a separately derived system or a non-separately derived system.

Separately Derived System (SDS): A generator is considered an SDS if there is no direct electrical connection (metallic path) between the generator’s output conductors and the service conductors, other than through the grounding and bonding path. This typically occurs when a generator feeds a transfer switch that opens the neutral conductor (a 4-pole transfer switch).

Grounding an SDS (250.30): For a separately derived system, the Master must:

59.Connect the system neutral to the grounding electrode system at the generator or at the first disconnecting means.
60.Bond the equipment grounding conductor to the system neutral at the same point.
61.Provide a grounding electrode conductor sized per Table 250.66 based on the largest ungrounded conductor.

Non-Separately Derived System: If the generator is connected to a transfer switch that does not switch the neutral (a 3-pole transfer switch), the generator is not an SDS. In this case, the generator’s neutral is solidly connected to the utility neutral, and the ground-fault current path is back to the utility source. The generator frame must be bonded to the equipment grounding conductor, but a separate grounding electrode is not required (though it is often recommended for lightning protection).

Generator Conductors (445.13): The ampacity of the conductors from the generator terminals must be not less than 115% of the generator’s nameplate current rating. This is a distinct rule from motor conductors.

Generator Protection (445.12): Generators must be protected from overloads. If the generator is driven by a prime mover (engine), the protective device must be rated to carry the rated current of the generator continuously, but must trip on short circuit.


1.7 Commercial and Industrial Applications

Feeder Taps for Motor Circuits (430.28): The NEC permits taps for motor branch circuits under specific conditions. A tap conductor must have an ampacity of at least one-third of the rating of the overcurrent device protecting the feeder, and must terminate in a single circuit breaker or set of fuses. The tap must be enclosed and not exceed 7.6 m (25 ft) in length.

VFD Installations (430.120-430.132): Variable frequency drives are treated as "power conversion equipment." The input conductors are sized per 430.122, which requires the branch-circuit conductor ampacity to be not less than 125% of the rated input current of the VFD. The output conductors (motor side) are sized per 430.22. The VFD’s internal overload protection is acceptable if it meets the requirements of 430.124.

Inspection Point: When inspecting a VFD installation, verify that the motor thermal protection is set to the motor nameplate FLC, not the VFD’s rated output current. A common mistake is leaving the VFD at its factory default of 100% of its own rating, which may not protect a smaller motor.


1.8 Code Navigation

ConceptNEC Reference
Motor FLC TablesTable 430.247 (DC), 430.248 (Single-Phase), 430.250 (Three-Phase)
Branch-Circuit Conductor Sizing430.22
Feeder Conductor Sizing430.24
Overload Sizing (SF ≥ 1.15)430.32(A)(1)
Overload Sizing (Standard)430.32(A)(2)
Short-Circuit Protection430.52, Table 430.52(B)
Standard Ampere RatingsTable 240.6(A)
Disconnect Location430.102
Controller Horsepower Rating430.83
Generator Conductor Sizing445.13
Generator Overcurrent Protection445.12
Grounding – Separately Derived Systems250.30
Grounding Electrode Conductor SizingTable 250.66
Motor Feeder Taps430.28
VFD Requirements430.120 – 430.132

1.9 Inspection and Supervision Points

As a Master, you are responsible for the final sign-off. Verify the following on every motor installation:

76.Nameplate vs. Table: Confirm the electrician used the Table FLC for conductor and breaker sizing, not the nameplate amps.
77.Overload Heater Size: Check that the overload relay heaters are sized per the nameplate current, and that the correct class of trip (Class 10, 20, or 30) is installed for the motor’s starting characteristics.
78.Disconnect in Sight: Measure the distance from the motor to the disconnect. If it exceeds 50 ft, it is a violation.
79.Locked-Rotor Protection: For motors with a code letter, verify the branch-circuit protection is not exceeding the maximum allowed by Table 430.52(B) Note.
80.Generator Neutral: Trace the neutral conductor. If the generator is an SDS, confirm the neutral is bonded to the ground at the generator and that a grounding electrode is present. If it is not an SDS, confirm the neutral is not bonded at the generator, to avoid parallel neutral-to-ground paths.

1.10 Common Exam Traps

The 125% vs. 115% Trap: Using 125% for overload protection on a standard motor (SF < 1.15). The correct value is 115%.
The Nameplate Trap: Using the motor nameplate current to size the branch-circuit conductors. The Code requires the Table FLC.
The "Next Size Up" Trap: Applying the "next size up" rule to overload relays (430.32) when the 140% cap is exceeded, or applying it to feeder conductors (which must be sized to the calculated value, not the next size up).
The Generator Trap: Sizing generator conductors at 125% instead of the required 115% (445.13).
The VFD Trap: Sizing the input conductors to the VFD based on the motor FLC, rather than the VFD’s rated input current (430.122).
The Feeder Trap: Forgetting to add the 25% of the largest motor in a multi-motor feeder calculation (430.24).

Preparing for the Texas Master Electrician license?

See the full licensing path, exam format, eligibility and application steps.

Read the Texas Master Electrician guide

Ready to test this chapter?

Practice with exam-aligned questions and timed simulations.

Start Practicing Free