Electrical Control Devices and Disconnecting Means
Master Electrician Practice study guide with diagrams.
Electrical Control Devices and Disconnecting Means
Learning Objectives
Upon completing this chapter, you will be able to:
1.1 The Hierarchy of Disconnecting Means: Service, Feeder, and Branch Circuit
A master electrician must understand the layered architecture of disconnecting means. The NEC requires that every conductor that is not part of a continuous raceway system be provided with a means to disconnect it from its source of supply. The hierarchy is as follows:
Master-Level Insight: For a service with multiple disconnects (the "six-handle rule"), the sum of the ratings of the disconnects must not be less than the calculated load, but no single disconnect is required to be rated higher than the maximum available fault current at the service. However, the service conductors must be protected at their ampacity. In practice, when you have a 400 A service calculated load, you cannot use two 200 A disconnects unless the service conductors are sized for the sum of the disconnects, which they typically are if sized for the calculated load.
1.2 Motor Disconnecting Means (Article 430, Part IX)
Motor disconnects are a frequent source of exam questions and field violations. The requirements are specific and unforgiving.
1.2.1 Location and Visibility
The motor disconnecting means must be located in sight from the motor and the driven machinery. "In sight" is defined as visible and not more than 15 m (50 ft) apart. If the disconnect is not in sight, the NEC requires additional means to prevent the motor from starting unexpectedly. This is typically achieved by a separate lockable disconnect at the motor location, or by a control circuit that automatically opens the motor contactor when the disconnect is opened.
Exam Trap: The 50 ft rule applies to the motor and the driven machinery. If the motor is driving a pump in a remote location, the disconnect must be within 50 ft of both. If a motor is in a mechanical room and the disconnect is outside the room but within 50 ft, it is compliant only if the motor is visible from the disconnect location. If the motor is behind a wall, it is not "in sight."
1.2.2 Disconnect Rating and Horsepower
The disconnect for a motor must have an ampere rating of at least 115% of the motor's full-load current (FLC) as listed in Tables 430.247 through 430.250. This is a minimum. However, the disconnect must also be rated for the motor's horsepower. A general-use switch with a horsepower rating can be used, but if the switch is not horsepower-rated, it must be a circuit breaker or a molded-case switch.
Critical Calculation: For a 25 hp, 460 V, three-phase motor, the FLC from Table 430.250 is 34 A. The disconnect must be rated at least 34 × 1.15 = 39.1 A. The next standard size is 40 A, but a 40 A safety switch is not typically horsepower-rated for a 25 hp motor. You must select a 60 A switch that is horsepower-rated for 25 hp at 460 V. The switch's ampere rating (60 A) is greater than the motor's FLC, and the horsepower rating meets the motor's rating.
1.2.3 Disconnect for the Controller
The motor controller (the contactor or starter) must also have a disconnecting means. In many installations, the branch circuit disconnect serves as the controller disconnect if it is in sight of the controller. If the controller is not in sight of the disconnect, a separate disconnect must be installed for the controller, or the controller must be capable of being disconnected by the branch circuit disconnect.
1.3 Control Devices: Contactors, Relays, and Motor Starters
1.3.1 Contactors and Relays
A contactor is a magnetically operated switching device. Relays are similar but typically used in control circuits. The NEC does not generally regulate the internal design of these devices, but it does regulate their installation and their overcurrent protection.
Key Rule (Article 430, Part VII): Control circuits must be protected against overcurrent. If a control circuit is tapped from the load side of the motor branch circuit protective device, the control circuit conductors must be protected at their ampacity. If the control circuit operates at 120 V and is tapped from a 480 V motor circuit, a control transformer is required. The secondary of the control transformer must be protected.
1.3.2 Motor Starters and Overload Relays
Motor starters combine a contactor with overload relays. The overload relays are designed to protect the motor, not the branch circuit conductors. The branch circuit overcurrent device protects the conductors, and the overload relay protects the motor.
Master-Level Insight: The overload relay must be sized based on the motor's nameplate full-load current (FLC), not the table value. The NEC permits the overload relay to be set at 125% of the motor nameplate current for motors with a service factor of 1.15 or more, or a temperature rise of 40 °C or less. For all other motors, the maximum is 115%. If the motor will not start, the overload relay can be increased to 140% of the nameplate current, but this is a design decision that must be documented.
1.4 Disconnecting Means for Services and Separately Derived Systems
1.4.1 Services (Article 230)
The service disconnect must be installed before the conductors enter the building, unless the service conductors are installed in accordance with 230.6 (underground) or 230.70 (inside a building). The disconnect must be a circuit breaker or a fused switch. The service disconnect must be marked "Suitable for Use as Service Equipment."
Voltage and Phase Considerations: For a 3-phase, 4-wire service, the disconnect must be a 3-pole switch or a 3-pole circuit breaker. The grounded conductor (neutral) must not be disconnected unless the disconnect is a 3-pole switch with a solid neutral, which is the standard configuration. The neutral is not fused or switched; it is connected to the neutral bus in the service equipment.
1.4.2 Separately Derived Systems (Article 250.30)
A separately derived system (SDS) is a source of power with no direct electrical connection to the supply conductors. Examples include a transformer (secondary side) and a generator (when the neutral is switched).
Disconnecting Means for an SDS: The disconnecting means for a transformer secondary must be installed on the secondary side. This disconnect must be rated for the secondary voltage and current. The grounding electrode conductor for the SDS must be connected to the neutral bus at the first disconnecting means or at the source (the transformer). The neutral must be bonded to the equipment grounding conductor at the SDS source or at the first disconnecting means.
Exam Trap: A generator that is a separately derived system (i.e., a generator with a transfer switch that switches the neutral) requires a disconnecting means that is rated for the generator's output. The generator must have a grounding electrode conductor connected to a grounding electrode, and the neutral must be bonded to the generator frame and the equipment grounding conductor.
Master-Level Insight: For a transformer supplying a 3-phase, 4-wire, 208Y/120 V panelboard from a 480 V source, the primary overcurrent protection is sized per 450.3. The secondary disconnect must be sized for the transformer's rated secondary current. If the transformer is rated 75 kVA, the secondary current at 208 V is 75,000 / (208 × 1.732) = 208 A. The secondary disconnect must be rated at least 208 A. The primary protection can be set at 125% of the primary current if the secondary protection is set at 125% of the secondary current.
1.5 Overcurrent Protection Coordination
1.5.1 Selective Coordination (Article 700.32, 701.27, 708.54)
For life safety systems (Article 700), legally required standby systems (Article 701), and critical operations power systems (Article 708), the overcurrent devices must be selectively coordinated. This means that when a fault occurs, only the device nearest the fault opens, and the upstream devices remain closed to keep power on to the rest of the system.
Master-Level Insight: Selective coordination is achieved by ensuring that the time-current curves of the upstream and downstream devices do not overlap. This is often done using fuses with a 2:1 ratio, or by using circuit breakers with adjustable trip units and performing a coordination study. The exam will test your knowledge of when coordination is required, not necessarily how to perform the study.
1.5.2 Motor Branch Circuit Protection
The motor branch circuit short-circuit and ground-fault protective device (MSCGFPD) is sized per 430.52. The maximum permitted setting for a non-time-delay fuse is 300% of the motor FLC, and for an inverse-time circuit breaker it is 250%. If the motor will not start, the next higher standard size is permitted.
Example Calculation: A 50 hp, 460 V motor has an FLC of 65 A. The maximum inverse-time circuit breaker is 65 × 2.5 = 162.5 A. The next standard size is 175 A. If the motor will not start, the breaker can be increased to 225 A (the next standard size above 162.5 A), but this is the absolute maximum.
1.6 Code Navigation: Where to Find It
| Topic | Code Reference |
|---|---|
| Service disconnecting means | Article 230, Part VI (230.70–230.85) |
| Six disconnect rule | 230.71 |
| Feeder disconnecting means | 215.2, 215.3 |
| Motor disconnecting means | 430.102, 430.103, 430.109 |
| Motor FLC tables | 430.247, 430.248, 430.250 |
| Motor branch circuit protection | 430.52, 430.53 |
| Overload protection | 430.32, 430.34 |
| Control circuits | 430.71, 430.72 |
| Separately derived systems | 250.30, 250.35 |
| Transformer protection | 450.3 |
| Selective coordination | 700.32, 701.27, 708.54 |
| Disconnect for controllers | 430.102(A) |
| Lockout/tagout capability | 110.25 (general), 430.103 (motors) |
1.7 Inspection and Supervision Points
As a master electrician, you are responsible for the final sign-off. On site, verify the following:
1.8 Common Exam Traps
1.9 Summary
The control and disconnection of electrical power is the single most important safety function in any installation. The NEC provides a comprehensive framework that ensures any conductor can be de-energized quickly and safely. As a master electrician, you must not only know the code sections but also understand the engineering principles behind them—the relationship between motor FLC, horsepower, and disconnect ratings; the necessity of selective coordination for life safety; and the critical distinction between a service and a separately derived system. Mastery of these concepts is essential for passing the Texas Master exam and for supervising safe, code-compliant installations.
Preparing for the Texas Master Electrician license?
See the full licensing path, exam format, eligibility and application steps.
Ready to test this chapter?
Practice with exam-aligned questions and timed simulations.
Start Practicing Free