Chapter III

Motors & Controls

Master Electrician Practice study guide with diagrams.

Motors & Controls — Vermont Master Electrician Exam Study Chapter

Learning Objectives

By the end of this chapter, you will be able to:

4.Apply the general requirements of Article 430 to motor branch circuits, feeders, and controllers, including sizing conductors and protection devices.
5.Calculate motor branch-circuit and feeder conductor ampacity using the correct percentage multipliers from Tables 430.22 and 430.24.
6.Select and size motor overload protection (OLs) per 430.32, including the service factor and temperature rise exceptions.
7.Distinguish between motor branch-circuit short-circuit and ground-fault protection (SCGFP) and overload protection, and size each correctly per 430.52 and 430.62.
8.Navigate the complex rules for motor controllers, disconnecting means, and control circuits (430.71–430.91).
9.Apply the special provisions for adjustable-speed drive systems (430.120–430.132) and generators (445).
10.Identify and correct common code violations and exam traps related to motor calculations and installations.

1.1 The Scope and Structure of Article 430

Article 430 is the single most important article for motor installations. It is a self-contained system of rules that governs every aspect of a motor circuit, from the branch-circuit conductors to the final overload protection. As a master electrician, you must understand that a motor circuit is not a simple "wire and breaker" scenario. It requires a layered approach:

14.Branch-Circuit Conductors (430.22): Sized to carry the motor's full-load current (FLC) plus a percentage for continuous operation.
15.Branch-Circuit Protection (430.52): The short-circuit and ground-fault protection device (SCGFP) — typically a fuse or circuit breaker — sized to allow the motor to start without opening, but to protect the circuit from faults.
16.Motor Overload Protection (430.32): A separate device (often a heater or electronic relay in a starter) designed to protect the motor itself from overheating due to mechanical overload or a stalled rotor.
17.Controller (430.81): The device that starts and stops the motor.
18.Disconnecting Means (430.102): A means to disconnect the motor and controller from all ungrounded supply conductors.

A common journeyman-level error is treating the motor circuit like a lighting circuit. A master understands that the SCGFP is not sized to protect the motor from overload; that is the job of the overload relay. The SCGFP is sized to protect the conductors and the motor from short circuits and ground faults, and it is deliberately sized larger than the running current to permit the high inrush current during starting.


1.2 Motor Full-Load Currents: Tables 430.247–430.250

The foundation of all motor calculations is the full-load current (FLC), not the nameplate current rating. The NEC mandates that you use the values from Tables 430.247 through 430.250 for all calculations involving conductor ampacity, disconnecting means, and SCGFP sizing.

Table 430.247: Direct-current motors.
Table 430.248: Single-phase alternating-current motors.
Table 430.249: Two-phase alternating-current motors (rarely used).
Table 430.250: Three-phase alternating-current motors.

Critical Master Point: The motor nameplate full-load amperes (FLA) is used only for sizing the overload protection (430.32). The table FLC is used for everything else. This is a classic exam trap. For example, a 10-hp, 3-phase, 460-volt motor may have a nameplate FLA of 13.2 A, but Table 430.250 gives an FLC of 14 A. You must use 14 A for conductor sizing and SCGFP sizing.


1.3 Sizing Branch-Circuit Conductors (430.22)

Motor Branch Circuit Sizing - NEC 430.22 Master Depth Motor Branch Circuit Sizing — NEC 430.22(A) 30 hp, 460 V, 3-phase • Table 430.250 FLC = 40 A • 125% × FLC = 50 A minimum ⚠ MASTER TRAPS: Nameplate FLC ≠ Table FLC (430.6(A)(1)) • 430.52 device protects conductor, not 240.4(G) STEP 1 Table 430.250 Motor: 30 hp, 460 V 3-phase induction FLC from Table: 40 A (not nameplate) ✗ Nameplate FLC = violation 430.6(A)(1) STEP 2 430.22(A) Conductor ampacity ≥ 125% of FLC 40 A × 1.25 = 50 A minimum Continuous-duty motor STEP 3 110.14(C) Termination temp: 75°C column Table 310.16: 8 AWG THWN = 50 A 60°C column would need 4 AWG STEP 4 240.6(A) 50 A is a standard size ✓ 8 AWG ✓ 50 A No upsizing needed MOTOR 30 hp • 460 V • 3φ M 430.52 Branch-Circuit Protection Inverse-time breaker: 250% × FLC = 100 A max Next standard size per 240.6(A) = 100 A ⚠ 240.4(G) — Motor circuits exempt Conductor protected by 430.52 device, not 240.4 100 A breaker protects 8 AWG (50 A) conductor Master Electrician Practice — NEC 430.22 motor branch circuit sizing • Vermont Division of Fire Safety / Prov • 2023 NEC

The general rule for a single motor is that the branch-circuit conductors must have an ampacity of not less than 125% of the motor's FLC from the tables.

Formula: Conductor Ampacity ≥ FLC (from Table 430.250) × 1.25

Example: A 25-hp, 3-phase, 208-volt motor has a table FLC of 74.8 A. The minimum conductor ampacity is 74.8 A × 1.25 = 93.5 A. You would select a conductor with a 75°C termination rating, such as a #3 AWG THHN (rated 100 A at 75°C), not a #4 AWG (rated 85 A).

Special Cases (430.22):

Continuous Duty, Multiple Motors on One Branch Circuit (430.22(C)): This is rare, but if you have a single branch circuit supplying several motors, the conductor ampacity must be the sum of 125% of the FLC of the highest-rated motor plus the sum of the FLCs of all other motors on that circuit.
Wound-Rotor Motors (430.22(B)): Conductors for the secondary circuit of a wound-rotor motor must have an ampacity of not less than 125% of the secondary full-load current.
Torque Motors (430.22(D)): These are special motors that are rated for continuous stall. The conductor ampacity must be at least 100% of the nameplate current rating.

1.4 Sizing Motor Feeders (430.24)

A feeder supplying two or more motors must have an ampacity sufficient for the sum of all the loads. The rule is:

Feeder Ampacity = (125% × FLC of the largest motor) + (Sum of FLCs of all other motors) + (Other loads on the feeder)

This is a critical calculation for commercial and industrial work. The 125% factor applies only to the single largest motor on the feeder, not to all of them.

Example: A feeder supplies three motors: a 10-hp (14 A), a 15-hp (21 A), and a 25-hp (34 A) at 460V, 3-phase. The feeder ampacity must be at least (34 A × 1.25) + 21 A + 14 A = 42.5 A + 35 A = 77.5 A. You would size the conductors for at least 77.5 A.

Important: This calculation is for the conductors. The feeder overcurrent protection is sized differently (see 430.62).


1.5 Overload Protection (430.31–430.40)

Overload protection is designed to protect the motor, the motor control apparatus, and the motor branch-circuit conductors against excessive heating due to motor overloads and failure to start.

Sizing Rules (430.32):

Motors with a marked service factor of 1.15 or greater, or a marked temperature rise of 40°C or less: The overload device must be sized at no more than 125% of the motor nameplate full-load current (FLA).
All other motors: The overload device must be sized at no more than 115% of the motor nameplate FLA.

Example: A motor has a nameplate FLA of 10 A and a service factor of 1.15. The maximum overload relay size is 10 A × 1.25 = 12.5 A. You would select the next standard size up if the relay is not adjustable, but you cannot exceed the 125% limit unless the relay is set to trip at or below 12.5 A.

The "Next Size Up" Rule (430.32(C)): If the motor is not overloaded when it is running, and the motor is not part of a group installation, you may use the next higher standard size of overload relay if the calculated value does not correspond to a standard size. However, the relay must be set to trip at no more than the calculated value. This is a common point of confusion.

Dual-Element Time-Delay Fuses as Overloads: In some cases, dual-element time-delay fuses can be used for overload protection, but they must be sized per 430.36 and are limited to 125% of the motor nameplate current for motors with a service factor of 1.15 or more.

Master Supervision Point: On site, always verify the motor nameplate service factor and temperature rise. A motor with a 1.0 service factor is common in modern, high-efficiency designs. These motors are much less forgiving, and the overloads must be set at 115% of nameplate, not 125%.


1.6 Branch-Circuit Short-Circuit and Ground-Fault Protection (430.51–430.58)

Motor SC/GF Protection (430.52) Motor Short-Circuit & Ground-Fault Protection — NEC 430.52 Table 430.52 — Maximum ratings for motor branch-circuit protection devices MOTOR FLC (Table 430.248) 40 A NEC 430.6(A)(1): Use table FLC, not nameplate, for SC/GF sizing. Nameplate is for overload (430.32). Non-Time-Delay Fuse 300% × 40 A = 120 A Time-Delay Fuse 175% × 40 A = 70 A Inverse-Time Breaker 250% × 40 A = 100 A Instantaneous- Trip Breaker 800% × 40 A = 320 A 430.52(C)(1) Exception 1 — Next Standard Size Up If the calculated value does not correspond to a standard rating (240.6), the next HIGHER standard size is permitted. Example: 70 A → 70 A standard. 120 A → 125 A standard. 100 A → 100 A standard. 320 A → 350 A standard. Only if the motor will not start with the lower-rated device. 430.52(C)(1) Exception 2 — Energy-Efficient Motors NEMA code letter marked on nameplate determines the locked-rotor current (NEC 430.7(B)). If code letter is unknown, 430.52(C)(1) Exception 2 allows the next size up ONLY for the specific conditions stated — verify code letter first. MASTER TRAP Percentages apply to Table 430.248 FLC, NOT the nameplate rating. MASTER TRAP 100 A device on 50 A conductor is LEGAL — 430.52 governs, not 240.4(B). MASTER TRAP 430.52 = SC/GF only. Overload protection is a separate 430.32 calculation. Master Electrician Practice — NEC 430.52 Motor SC/GF Protection (Vermont Division of Fire Safety / 2023 NEC)

This is the device that protects the branch-circuit conductors, the controller, and the motor against overcurrents due to short circuits and ground faults. It is not an overload device.

Sizing Rules (430.52): The maximum rating or setting of the SCGFP is based on a percentage of the motor FLC from the tables. Table 430.52 provides these percentages:

Motor TypeNon-Time-Delay FuseDual-Element Time-Delay FuseInstantaneous Trip BreakerInverse Time Breaker
**Single-Phase, All Types**300%175%800%250%
**3-Phase, Squirrel Cage (other than Design B)**300%175%800%250%
**3-Phase, Design B Energy-Efficient**300%175%1100%250%
**Synchronous**300%175%800%250%
**Wound-Rotor**150%150%800%150%
**Direct-Current (Constant Speed)**150%150%250%150%

Example: A 15-hp, 3-phase, 460-volt Design B motor has an FLC of 21 A. Using an inverse-time circuit breaker, the maximum SCGFP rating is 21 A × 250% = 52.5 A. You would select a 50 A breaker. If you use a dual-element time-delay fuse, the maximum is 21 A × 175% = 36.75 A, so you would select a 35 A fuse.

The "Next Size Up" Rule (430.52(C)(1) Ex. 1): If the calculated value does not correspond to a standard rating, you may go up to the next standard size. However, this is a maximum limit. You can always use a smaller device, provided it allows the motor to start.

Master Supervision Point: The most common field violation is oversizing the SCGFP. A 60 A breaker on the 15-hp motor above would be a code violation. The breaker is there to protect the conductors from a short circuit; a larger breaker may not open fast enough to prevent catastrophic damage to the motor and conductors.


1.7 Sizing Feeder Overcurrent Protection (430.62)

The feeder SCGFP is sized to protect the feeder conductors. The rule is more complex than for a single motor.

Rule (430.62(A)): The feeder protection device must be rated to protect the feeder conductors, but it must also be sized to allow the largest motor on the feeder to start. The maximum rating is:

Feeder SCGFP Max = (Largest Motor SCGFP rating per 430.52) + (Sum of FLCs of all other motors)

Example: Using the feeder from Section 1.4 (10-hp, 15-hp, 25-hp motors), and assuming all are Design B with inverse-time breakers:

Largest motor (25-hp, 34 A): 34 A × 250% = 85 A.
Sum of other FLCs: 14 A + 21 A = 35 A.
Maximum feeder breaker size: 85 A + 35 A = 120 A.

You would select a 100 A or 110 A breaker, whichever is standard, but you cannot exceed 120 A. Note that you do not add 125% of the largest motor's FLC here; you use the maximum SCGFP rating for that motor.


1.8 Controllers and Disconnecting Means (430.81–430.110)

Controllers (430.81): A controller is any switch or device that is normally used to start and stop a motor. It must be rated for the horsepower of the motor, or be a listed motor controller. A simple snap switch (light switch) can only be used for motors rated at 2 hp or less and 300 V or less (430.83(C)).

Disconnecting Means (430.102):

Controller Disconnect (430.102(A)): A disconnecting means must be provided for the controller. It must be in sight from the controller location.
Motor Disconnect (430.102(B)): A disconnecting means must be provided for the motor. It must be in sight from the motor location. The controller disconnect can serve as the motor disconnect if it is in sight from the motor.

The "In Sight" Rule (Article 100): "In sight" means the equipment is visible and not more than 15 m (50 ft) apart. This is a critical definition for a master to enforce on site.

Disconnect Rating (430.109): The disconnecting means must have a horsepower rating not less than the motor's horsepower. A general-use switch with a horsepower rating can be used. For motors over 100 hp, the disconnecting means must be a motor-circuit switch, a molded-case circuit breaker, or a listed industrial control panel.


1.9 Adjustable-Speed Drive Systems (430.120–430.132)

VFD Branch Circuit Sizing (430.122) VFD Branch Circuit Sizing — NEC 430.122(A) Drive Input Rating vs Motor FLC — Master Depth Comparison BRANCH CIRCUIT Feeder Source OCPD 430.130 VFD DRIVE Input Rating Nameplate: 48A SIZE CONDUCTORS: 48A × 125% = 60A MOTOR 25 HP, 3-Phase BYPASS MODE OVERLOAD 430.32 ⚠ MASTER TRAP 1 Using motor Table 430.250 FLC for branch conductor sizing when drive input is given. ⚠ MASTER TRAP 2 Forgetting 430.122 125% applies to drive input current — not motor FLC math. ✓ CORRECT: 48A × 1.25 = 60A → #6 AWG @ 75°C per Table 310.16 (before adjustments) Bypass mode: motor loses drive electronic protection → separate overload relay sized per 430.32 with 430.6(A)(2) nameplate current. Master Electrician Practice — NEC 430.122(A) VFD Branch Circuit Sizing | Vermont Division of Fire Safety / Prov | 2023 NEC

Variable Frequency Drives (VFDs) are ubiquitous in modern commercial and industrial installations. Article 430, Part X, has specific requirements.

430.122 Conductors: The ampacity of the conductors supplying a VFD must be at least 125% of the rated input current of the drive.
430.124 Overload Protection: The VFD must provide motor overload protection. If the drive is set up to do this, separate overload relays are not required.
430.126 Branch-Circuit Protection: The SCGFP for the drive is sized based on the drive's input current rating, not the motor's FLC. This is a common mistake.
430.128 Disconnecting Means: The disconnect must be in sight from the drive.

Master Supervision Point: VFDs generate harmonic currents. The neutral conductor in a 4-wire system supplying nonlinear loads must be counted as a current-carrying conductor for derating purposes (310.15(E)). This is a subtle but critical detail for feeder sizing to VFD panels.


1.10 Generators (Article 445)

Generators are treated as separately derived systems when they have no direct connection to the utility source. Key points for a master:

445.13 Ampacity of Conductors: The conductors from the generator terminals to the first overcurrent device must have an ampacity of at least 115% of the generator's nameplate current rating.
445.18 Disconnecting Means: Generators must have a disconnecting means that is capable of being locked in the open position.
Grounding (250.30): A separately derived system (like a generator with a transfer switch) must have its neutral grounded at the source (the generator) or at the first disconnecting means, but not both.

Code Navigation: Where to Find It

ConceptNEC Reference
Motor FLC Tables430.247, 430.248, 430.249, 430.250
Branch-Circuit Conductors430.22
Feeder Conductors430.24
Overload Protection430.32, 430.36
SCGFP (Branch)430.52, Table 430.52
SCGFP (Feeder)430.62
Controllers430.81, 430.83
Disconnecting Means430.102, 430.109
Control Circuits430.71, 430.72
Adjustable-Speed Drives430.120 – 430.132
Generators445
"In Sight" DefinitionArticle 100
Conductor Derating for Nonlinear Loads310.15(E)
Grounding Separately Derived Systems250.30

Inspection and Supervision Points

As a master, you are responsible for the final sign-off. Here is your checklist:

103.Verify Table FLC vs. Nameplate FLA: Check the calculations. Ensure the electrician used Table 430.250 for conductor sizing, not the nameplate.
104.Check Overload Heater Sizes: Look at the motor nameplate for the service factor. If it is 1.15 or less, the overloads must be sized at 125% or 115% of the nameplate current, respectively. Verify the actual heater elements or electronic settings in the starter.
105.Confirm the SCGFP is Not Oversized: A breaker that is too large is a silent hazard. Verify the size against Table 430.52.
106.Verify Disconnects are "In Sight": Walk the distance. If it is more than 50 ft, or if a wall or other obstruction blocks the view, it is a violation.
107.Check the VFD Input Current: For VFD installations, confirm the branch circuit and SCGFP are sized on the drive's input rating, not the motor's FLC.

Common Exam Traps

110.The Nameplate Trap: Using the motor nameplate FLA to size branch conductors or the SCGFP. Always use Table 430.250 values for these.
111.The 125% Trap: Applying the 125% factor to all motors on a feeder, rather than only the largest one.
112.The Overload Trap: Forgetting to check the service factor. A motor with a 1.0 service factor requires overloads at 115%, not 125%.
113.The "Next Size Up" Trap: Assuming you can always go up to the next standard size for SCGFP. The "next size up" rule is an exception, and it only applies if the calculated value does not correspond to a standard size. You cannot use it to arbitrarily increase the protection.
114.The VFD Trap: Sizing the branch circuit for a VFD based on the motor FLC instead of the drive's input current rating.
115.The Disconnect Trap: Forgetting that a motor and its controller must each have a disconnecting means, and that the controller disconnect must be in sight from the controller, and the motor disconnect must be in sight from the motor.

Preparing for the Vermont Master Electrician license?

See the full licensing path, exam format, eligibility and application steps.

Read the Vermont Master Electrician guide

Ready to test this chapter?

Practice with exam-aligned questions and timed simulations.

Start Practicing Free